NEWS
STORAGE
OCTOBER 2026
A battery energy storage system (BESS) is described by two quantities. Power, in megawatts (MW), is what it can inject into the grid at any given moment. Energy, in megawatt-hours (MWh), is what it can deliver on a full charge. The ratio between the two is the duration: a 100 MW, 400 MWh system sustains its maximum power for four hours.
The difference has economic consequences. Law 21.505 of 2022 brought storage into the capacity market, and DS 70/2023, which amended the capacity transfer regulation (DS 62/2006), set out how its contribution is calculated: the initial capacity of a storage system is its maximum power multiplied by a percentage that depends on the number of hours it can sustain injection. That initial capacity is the starting point for its sufficiency capacity, which is used to determine capacity payments.
Two projects with the same MW but different durations do not receive the same recognition. That is why, in a project fact sheet, power should always be accompanied by energy or duration.
Sources: Supreme Decree 70/2023 of the Ministry of Energy, amending DS 62/2006 (Diario Oficial, June 5, 2024). Law 21.505 (2022), according to an analysis by Garrigues (June 4, 2024).
POWER SYSTEM
OCTOBER 2026
When a zone's generation exceeds the capacity of the lines connecting it to consumption centers, part of that energy cannot be injected into the grid: this is curtailment. In 2025 it reached 6,205 GWh of solar, wind and hydro generation, a figure similar to 2024 (−0.3%) and 133% higher than in 2023. Antofagasta accounted for 48.3% and Atacama for 28.4%, and the main cause was transmission constraints.
Storage already plays a role: the batteries in operation made it possible to use nearly 2 TWh that would otherwise have been curtailed; without them, curtailment would have reached about 8,200 GWh. The market is responding: at the end of June 2026, 14 battery storage projects accounted for 48.9% of the 3,176.9 MW in the commissioning period at the Coordinador Eléctrico Nacional (Chile's grid operator).
The Kimal–Lo Aguirre direct current line (1,346 km and about US$1.5 billion) will connect Antofagasta with the Santiago Metropolitan Region. In September 2026 it was 20% complete, and its commercial operation is projected for 2029. Until then, a storage system located upstream of the congestion can charge when the grid is saturated and inject when there is capacity; its revenue will depend on the price difference between those hours and on how many other systems compete for them.
Sources: Broker & Trader Energy Chile, cited by Reporte Minero (January 21, 2026); Coordinador Eléctrico Nacional, cited by Reporte Minero (August 4, 2026); Reporte Minero (September 10, 2026).
REGULATION
OCTOBER 2026
PMGDs are power plants of up to 9 MW connected to distribution networks, governed by the regulation on small-scale generation (DS 88/2019). Supreme Decree 1/2026 of the Ministry of Energy, published in the Diario Oficial on June 13, 2026, amended that regulation to include storage systems.
For storage, the decree sets three core rules: it may opt into the price stabilization mechanism; its withdrawals for charging are valued under the same pricing regime it has chosen; and those withdrawals are not subject to the charges paid by end customers. At the same time, the distribution company gives priority to its end customers' withdrawals over the charging of storage systems.
The amended text also regulates the choice of pricing regime. Each project chooses between the instantaneous marginal cost and the stabilized price, and notifies the Coordinador of its choice after being declared under construction and at least one month before starting operation; if it makes no choice, the marginal cost applies. Each regime remains in place for at least one year, and changing it requires six months' notice. Under the stabilized regime, energy is valued at the basic price for each time interval, which the Ministry sets by decree based on a report from the CNE (National Energy Commission), and differences are settled through the MEP Balance (Saldo MEP) in twelve installments. A PMGD that modifies its connection or operating conditions must declare it in its Grid Connection Request (Solicitud de Conexión a la Red, SCR).
For a PMGD already in operation, adding storage requires reviewing three areas at once: the pricing regime, the treatment of charging energy and the connection request.
Source: Supreme Decree 1/2026 of the Ministry of Energy, Diario Oficial No. 44,474 (June 13, 2026); articles 9, 9 bis, 9 ter, 12, 14, 17, 37 and 43 of the amended regulation.